DS16

Push-in Din-Rail TB, Rated voltage : 1000 V,Rated current: 76 A, connector method: Push-in connector, Number of connectors: 2, Number of potentials: 1, Cross section: 0.5 mm² – 25 mm², AWG: 20 – 4, Width: 12.2 mm, Height: 52mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15

poles

01P

Описание


Overview

Connection method Push in connection
Number of potentials 1
Number of rows 1
number of connections 2
electric potentials 1
Open-end side panels Yes
Insulation Materials PA
Flame retardant grade, in line with UL 94 V0
Application field Railway industry, mechanical engineering, factory engineering, process industry, etc.
color Gray

Dimension

NS 35/7,5 Height 53.3mm
End plate width 2.2mm
NS 35/15 Height 60.8mm
length 75.4mm
width 12.2mm
Height 52mm

Wiring data

Strip length 18mm
Conductor cross section solid 0.5~25mm²
Conductor cross section flexible 0.5~16mm²
Conductor cross section flexible AWG 20~4
Conductor cross section solid AWG 20~4

Environmental conditions

Ambient temperature (operation) -40 °C ~ 105 °C(depending on derating curve)
Ambient temperature (storage / transport) -5 °C ~ 70 °C
Ambient temperature (assembly) -5 °C ~ 70 °C
Ambient temperature (execution) -5 °C ~ 70 °C
Relative humidity (storage/transport) 25%~75%

UL Electrical parameters

standard test UL1059
Rated voltage (Use Group B) 600V
Rated current (Use Group B) 85A

IEC Electrical parameters

standard test IEC60947-7-1
Pollution level 3
Overvoltage level III
Insulating material group I
Rated voltage (III / 3) 1000V
Rated current (III / 3) 76A
Rated surge voltage 8KV

Safety test

Anti-finger touch IP20

Mechanical performance test

Mechanical performance test Passed the test
Bending test rotation speed 10rpm
Bending test 135
Bend test lead cross section/weight 0.5mm²/0.3Kg
25mm²/4.5kg
16mm²/2.9Kg
Tensile test results Passed the test
Conductor cross-section tensile test/set point traction 0.5mm²/20N
16mm²/100N
25mm²/135N

Environmental protection

REACh SVHC Lead 7439-92-1
RoHS No excessive harmful substances

Electrical performance test

Requirement, voltage drop ≤3.2mV
Voltage drop test results Passed the test
Temperature rise test result Passed the test